Home > Sites > OT B2A CAMERON > Battery Voltage
FerIT Offtake: OT B2A CAMERON
Tag: Battery Voltage
  • Properties
  • Event
    • History
    • Integration
    • Trend
  • Alarm
    • History
    • Actions
    • Action Log
  • Rating Tables

Properties


General
Tag ID 24317 Tag Name BATT_VOLT
Tag Description Battery Voltage Tag Value 13.213623
Tag Units V Tag Time 01.04.2026 17:34:26
Site Name OT B2A CAMERON Attribute Type
Caption Format 6.2
Minimum Value 0.00 Maximum Value 4.00
Sequence Number Display Y
Setpoint N
Event
Log Events Y Change Amount 0.1
Log Interval 600 Log Count 6182
Log Last Value 13.21 Log Last Time 01.04.2026 17:34:26
GUI Change Amount
Alarm
Enabled Y Logged Y
High High 16.50 High 16.00
Low 11.50 Low Low 11.00
Priority High Deadband 0.0
ROC Rise ROC Fall
ROC Time (Sec) Alarm Count 1
Address
Collection System Production System Data Source RTU 5000
Data Table GENERAL FLOATS Row Number 5
Column Number 1 Data Type
Scaling
Raw Value 13213.623 Zero 0.0
Span 1.0 Range 1000.0


SCADAConnect Web version 2.10.0